How do you read a KKS code?

Last updated:

Short Answer — KKS Code Structure

A KKS code is read from left to right on four levels: plant (0), system (1), equipment unit (2) and component (3). For example, in the code 1 LAC10 AP001 KP01, 1 indicates the unit number, LAC10 the feedwater pump system, AP001 the pump unit in that system, and KP01 the pump itself within the unit.

Which blocks does a KKS code contain?

In KKS, the position of each character is fixed; the standard defines whether a letter or a digit appears in each position. This means the code can be decoded even if the spaces are removed. In the table below, A stands for a letter and N for a digit.

LevelCharacter patternExampleWhat does it tell you?
0 – PlantLetter or digit as defined by the project1Unit (block) or common facility
1 – SystemN + AAA + NNLAC10Which system, and which section of it
2 – Equipment unitAA + NNN (+ optional A)AP001Device or circuit in the system
3 – ComponentAA + NNKP01Part inside the device

The first digit at system level distinguishes between several identical systems where there is more than one; for a single system it may be left blank. The general logic and history of the code are explained in the what is a KKS code entry.

How is a sample code decoded step by step?

Let us read the code 1 LAC10 AP001 KP01 from left to right:

  1. 1: Plant level. The code belongs to unit 1. In some projects this field is written with more than one character; the format is set by the project's coding manual.
  2. L: Main group, steam-water-gas cycle.
  3. LA: Group, feedwater system.
  4. LAC: Subgroup, feedwater pump system.
  5. 10: Numbering within the system; distinguishes parallel lines or sections.
  6. AP001: AP indicates the pump unit (the pump, drive and connecting elements as a whole), 001 the serial number of this unit.
  7. KP01: K indicates mechanical components, KP the pump itself, 01 its sequence number.

The electric motor or measuring element inside the same pump unit carries the same code up to AP001; only the component block changes. This makes it clear from the code that a motor in one crate and a pump casing in another crate belong to the same unit.

What are the common letter codes?

  • Main groups: C instrumentation and control, J nuclear heat generation, K nuclear auxiliary systems, L steam-water-gas cycle, M main machine sets, P cooling water systems, U structures.
  • Equipment units: AA valve, AC heat exchanger, AP pump unit, BB tank and vessel, BR piping, CT temperature measurement circuit, CP pressure measurement circuit.
  • Components: such as KA valve body, KP pump, QT thermocouple protection tube.

Location codes, on the other hand, start with main group U, followed by building, floor and room information. This code tells you which building and room on site a crate is going to.

What do reading errors lead to in logistics?

  • Skipping the unit number: The same pump in units 1 and 2 carries the same code apart from the plant level. If this digit is dropped, the equipment goes into the wrong unit's store.
  • Confusing letters and digits: In KKS, the letters I and O are not used so that they are not confused with 1 and 0. If an O appears on a label, it should be read as zero.
  • Mistaking the unit code for a component: For equipment arriving in multiple packages, if it is overlooked that all packages belong to the same AP001 unit, people start searching for "missing" parts.
  • Not entering a revised code in the documents: If the packing list and the crate label show different codes, the equipment is held up at site inspection.

How the code is written on crate labels and documents is explained in the using the KKS code on packaging entry, and the code's role in traceability in the traceability of nuclear equipment entry. At receipt, the code is compared one-to-one with the code in the equipment passport.

How does Voltim Global support this?

In nuclear project shipments, Voltim Global compares the KKS code on the crate label with the packing list and the passport at loading; if there is a mismatch, it notifies the shipper before the vehicle sets off.

Frequently Asked Questions

Are the spaces in a KKS code mandatory?
The spaces are there to separate the levels visually; since the character positions are fixed, the code can also be decoded without spaces. However, the same notation should be used on the label, the packing list and in the warehouse system. If one keeps records with spaces and another without, barcode and text matching may fail. The project's coding manual specifies which format is to be used.
Can the same KKS code exist in two different units?
The system, equipment and component blocks are identical in units that share the same design. The only field that distinguishes the two codes is the plant level. For this reason, in multi-unit power plants, the unit number should never be abbreviated or omitted on shipping documents or crate labels. For equipment belonging to common facilities, the plant level takes a separate value indicating the common area instead of a unit.